Introduction to common methods for inspection and maintenance of plastic machinery inverters

In the daily maintenance process of the inverter, various problems such as peripheral line problems, poor parameter setting or mechanical failure are often encountered. If the inverter is faulty, how to determine which part of the problem is a part, here is a brief introduction.

First, static testing

1, test rectifier circuit

Find the P and N terminals of the internal DC power supply of the inverter, adjust the multimeter to the resistance X10, the red bar to P, and the black bar to R, S, T, respectively, should have a resistance of about tens of ohms. And basically balanced. Instead, the black bar is connected to the P terminal, and the red bar is sequentially connected to R, S, and T, and has a resistance close to infinity. The red bar is connected to the N-end and the above steps are repeated. The same result should be obtained. If there are the following results, it can be determined that the circuit has an abnormality, a. The three-phase unbalance of the resistance value can explain the rectifier bridge failure. B. When the red bar is connected to the P terminal, the resistance is infinite, and it can be concluded that the rectifier bridge is faulty or the starting resistor is faulty.

2, test the inverter circuit

Connect the red bar to the P terminal, and the black bar is connected to U, V, and W respectively. There should be a resistance of several tens of ohms, and the resistance values ​​of the phases are basically the same, and the inversion should be infinite. Connect the black bar to the N terminal. Repeat the above steps to get the same result. Otherwise, the inverter module can be determined to be faulty.

Second, dynamic testing

After the static test result is normal, the dynamic test can be performed, that is, the power test machine is powered on. You must pay attention to the following points before and after power-on:

1. Before power-on, you must confirm whether the input voltage is wrong. If the 380V power supply is connected to the 220V inverter, a bomber (explosive capacitor, varistor, module, etc.) will appear.

2. Check if the connection ports of the inverter are connected correctly, and if the connection is loose, the connection may be abnormal, which may cause the inverter to malfunction. In severe cases, a bomber may occur.

3. After the power is turned on, the fault display content is detected, and the fault and the cause are preliminarily determined.

4. If the fault is not displayed, first check whether the parameter is abnormal, and after returning the parameter, start the inverter under no-load (no motor), and test the U, V, W three-phase output voltage value. If there is a phase loss, three-phase unbalance, etc., the module or the drive board is faulty.

5, in the case of normal output voltage (no phase loss, three-phase balance), load test. When testing, it is best to test at full load.

Third, fault determination

1, the rectifier module is damaged

Usually caused by grid voltage or internal short circuit. Replace the rectifier bridge with the internal short circuit removed. When dealing with faults on site, it is important to check the user's power grid conditions, such as grid voltage, and whether there are equipment such as welding machines that are polluting the power grid.

2, the inverter module is damaged

Generally caused by motor or cable damage and drive circuit failure. After repairing the drive circuit, the drive waveform is replaced and the module is replaced. After replacing the engine board in the field service, you must also pay attention to check the motor and connecting cables. Run the frequency converter without any faults.

3, no display after power-on

Generally, the switching power supply is damaged or the soft charging circuit is damaged, so that the DC circuit is not caused by DC power. If the starting resistance is damaged, the panel may be damaged.

4. Overvoltage or undervoltage is displayed after power-on

Generally, due to the input phase loss, the circuit is aging and the board is exposed to moisture. Find out its voltage detection circuit and detection points and replace the damaged device.

5. Overcurrent or ground short circuit after power-on

This is generally due to damage to the current sensing circuit. Such as Hall components, op amps, etc.

6, start to display over current

Usually caused by damage to the drive circuit or inverter module.

7. The no-load output voltage is normal, and the overload or over current is displayed after loading.

This kind of situation is generally caused by improper parameter setting or aging of the drive circuit and module damage.

Customized clear plastic PVC PET folding packaging boxes for product packing

1 We are manufacturer,We can provide competitive price!
2 We have been in this line for more than 10 years-Rich experience,Advanced technology, Excellent workmanship!
3 We run flexibly-OEM and ODM orders are acceptable!

Other Details
1:Our products can be widely used in various fields such as Food packaging(Macaron Packaging, Sushi Container,Cake Boxes, Biscuit Tray,Chocolate Tray,Sea Food Tray,Meal Tray, Salad Bowl), Medical Packaging, Cosmetic packaging, Stationary packaging, 
Electronic products packaging, Gift packaging, Hardware tools packaging, products displaying etc.


2:Any size and colors are available according to your request .


3:Various types of materials including PET /CPET / PS / PP / PVC /PETG /PLA Starch,Biodegradable/Flocking are available!


4:Logo and other details can be hot stamping.


5:We can provide products of high quality at a competitive price as we have our own factory!


6:OEM &ODM are welcomed!


7:If you are interested in our products, please feel free to contact us or visit our factory, we`ll be at your service any time.

Customized clear plastic PVC PET folding packaging boxes for product packing

 Folding packaging boxes

Customized clear plastic PVC PET folding packaging boxes for product packingCustomized clear plastic PVC PET folding packaging boxes for product packing

 

Product Name Customized clear plastic PVC PET folding packaging boxes for product packing
Printing Color CMYK + white + PMS
Box Closure auto-bottom closure/ any customized closure accepted.
Special Technology Foil stamping, frosted effect, glossy finish, matte finish.
Samples clear sample is free without shipping, can provide 2 or 3 pieces.
Sample lead time 1 or 2 days for clear samples.
Production lead time 10 to 15 days, depends on order quantity.
Trade term EXW, FOB, CIF, C&F, DDP
Payment term 30% deposit, balance to be paid before shipment.

 

 

            RELATED PRODUCTS

 

Customized Service

 

 

Other Plastic Packaging Products

Round Gift Box,Plastic Food Packaging,Plastic Packaging Products,Customized Paper Folding Boxes

Shandong Top Leader Plastic Packing CO., LTD , https://www.sdzlplastic.com

Posted on